The FAAST LT-200 EB 2-channel device is an advanced active fire detection system, equipped with 2 completely separate channels, each with a laser smoke detector. It’s possible to connect up to two pipelines per channel. The FAAST LT 2 has a preconfigured esserbus coupler for connection to the esserbus ring bus line.
Features & Benefits:- 2-channel system for connecting max. 2 pipelines per channel
- 2 independent measuring chambers, each with a fan, filter, sensor, and separate air outlets
- Built-in and preconfigured esserbus coupler
- 2 highly sensitive laser sensors for highest stability
- 9 different adjustable sensitivity levels from 0.07% LD/m (separately adjustable per channel)
- Programmable pre-alarm levels for each individual channel
- Sophisticated detection algorithms reduce false alarms
- PipeIQ software for intuitive system layout, configuration, and maintenance in a
- simple LED overview with a detailed fault indicator
- Unique airflow pendulum shows the current airflow of the individual channel
- A fan for each channel, 10 individually-adjustable fan speeds
- Operating volume from 28 dB(A) (at fan level 1)
- Integrated event memory up to 2244 events
- Ultrasonic flow rate sensor for accurate pipe flow measurement evaluable for each channel
- USB interface
- IP 65 protection rating
- 2 removable integrated filter units
- Operating menu in 24 languages
- Set-up of a Type B two-detector dependency in accordance with DIN VDE 0833-2 and VdS 2095 possible
- Approved for the requirements of EN 54-20 classes A, B, and C with the following information:
- Max. 200 m pipeline length per channel
- Max. 20 holes for class C per channel
- Max. 10 holes for class B per channel
- Max. 3 holes for class A per channel
- Approved for the requirements of EN 54-20 classes A, B, C using the pre-alarm with the following information:
- Max. 120 m pipeline length per channel
- Max. 12 holes for class C per channel
- Max. 4 holes for class B per channel