    Signaling line circuit (SLC) personality modules provide communication between S3 Series fire alarm control panels and signaling line circuit devices.

    Überblick

    Signaling line circuit (SLC) personality modules provide communication between S3 Series fire alarm control panels and signaling line circuit devices. They offer one SLC loop in Class B or Class A wiring and support up to 318 Velociti® devices (159 sensors and 159 modules) and up to 198 CLIP devices (99 sensors and 99 modules).

    Features & Benefits:
    • Supports Class A or Class B Wiring
    • Offers a simple, plug-in installation feature
    • Listed per ANSI/UL standard 864 9th edition
    Certifications:
    • UL Listed: S1869
    • FM Approved
    • MEA FDNY: COA # 6162
    • CSFM: 7165-1703:0176
    • City of Chicago Approved: Class 1
    • Reference Certificate of Compliance: VMA 45894-02C