Annunciators & Keypads

ANN-RLED Annunciator Module

The Notifier N-ANN-LED annunciator modules provides LED annunciation of general system faults and input zones/points when used with a compatible Fire Alarm Control Panel. The N-ANN-LED is supplied with Canadian Firewarden FACPs as required by ULC.

The Notifier N-ANN-LED annunciator modules provides LED annunciation of general system faults and input zones/points when used with a compatible Fire Alarm Control Panel (FACP). The N-ANNLED module provides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones or addressable points. N-ANN-RLED has red LEDs only for alarm communication of up to 30 addressable points.

The N-ANN-LED is supplied with Canadian Firewarden FACPs as required by ULC. The N-ANN-LED and the FACP communicate over a two-wire serial interface employing the ANN-BUS communication format. An additional two wires are used for 24-volt DC power. A single four-conductor unshielded cable may be used for both power and data communications. Up to eight ANN-BUS devices may be connected to the ANNBUS of each FACP.

Features & Benefits:
  • ANN-LED connects to the ANN-BUS terminal on the FACP and requires minimal programming.
  • Includes three LEDs for each zone: Alarm, Trouble and Supervisory.
  • Compatible with the MS-9050UD, MS-5UD-3, MS-10UD-7, MRP-2001, MRP-2002, MS9200UDLS version 4.0 or greater, MS-9600LS and MS-9600UDLS.
  • Can be remotely located up to 6,000 feet (1,829 m) from the panel.
  • May be powered by 24 VDC from the host FACP or by remote power supply.
Certifications:
  • UL: S635
  • ULC: S635 (N-ANN-LED only)
  • FM approved
  • CSFM: 7120-0028:0259
  • MEA: 333-07-E
  • Fire Dept of NY: COA #6177

Others

  • Maximum Operating Humidity
    • 93 Percentage
  • Maximum Operating Voltage
    • 24
  • Alarm Current
    • 68 milliampere
    • 28 milliampere
  • Number of Zones
    • 10
  • Light Bulb Type
    • LED

Others

  • Maximum Operating Humidity
    • 93 Percentage
  • Maximum Operating Voltage
    • 24
  • Alarm Current
    • 68 milliampere
    • 28 milliampere
  • Number of Zones
    • 10
  • Light Bulb Type
    • LED
  • Number of Zones : 10
  • Light Bulb Type : LED
  • Alarm Current : 68 milliampere|28 milliampere
  • Maximum Operating Humidity : 93 Percentage
  • Maximum Operating Voltage : 24
Sort
Installation Instructions
Document Title
File Size
Date Added
Asset Language
Content Type
Data Sheet
Document Title
File Size
Date Added
Asset Language
Content Type
Document Title
File Size
Date Added
Asset Language
Content Type
Image
SKU
Description
alt
ANN-RLED-W
ANN-RLED Annunciator Module, 18 to 28VDC, Alarm- 68 mA, Standby-28 mA