Annunciators & Keypads

N-ANN-LED Annunciator Module

The N-ANN-LED annunciator module provides LED annunciation of general system faults and input zones/points when used with a compatible Fire Alarm Control Panel (FACP).

The N-ANN-LED annunciator module provides LED annunciation of general system faults and input zones/points when used with a compatible Fire Alarm Control Panel (FACP). The N-ANNLED module provides alarm (red), trouble (yellow) and supervisory (yellow) indication for up to ten input zones or addressable points. N-ANN-RLED has red LEDs only for alarm communication of up to 30 addressable points. The N-ANN-LED is supplied standard with Canadian Fire warden FACPs as required by ULC.

The N-ANN-LED and the FACP communicate over a two-wire serial interface employing the ANN-BUS communication format. An additional two wires are used for 24-volt DC power. A single four-conductor unshielded cable may be used for both power and data communications. Up to eight ANN-BUS devices may be connected to the ANNBUS of each FACP

Features & Benefits:
  • N-ANN-LED connects to the ANN-BUS terminal on the FACP and requires minimal programming
  • Includes three LEDs for each zone: Alarm, Trouble and Supervisory. N-ANNRLED includes all red LEDs for alarm only annunciation
  • Compatible with the NFW-50(C), NFW2-100(C), SFP5UD(C), SFP-10UD(C), RP-2001(C), RP-2002(C)
  • Can be remotely located up to 6,000 feet (1,829 m) from the panel
  • May be powered by 24 V DC from the host FACP or by remote power supply (requires 24 V DC).
Certifications:
  • UL: S635
  • ULC: S635 (N-ANN-LED only)
  • FM approved
  • CSFM: 7120-0028:0259
  • MEA: 333-07-E
  • Fire Dept of NY: COA #6177

Others

  • Alarm Current
    • 68 milliampere
    • 28 milliampere
  • Minimum Operating Humidity
    • ±2 Percentage
  • Maximum Wiring Distance
    • 6000 foot
  • Maximum Operating Humidity
    • ±93 Percentage
  • Light Bulb Type
    • LED
  • Addressing Style
    • ANN-Bus Unique
  • Number of Zones
    • 10 Zones

Others

  • Alarm Current
    • 68 milliampere
    • 28 milliampere
  • Minimum Operating Humidity
    • ±2 Percentage
  • Maximum Wiring Distance
    • 6000 foot
  • Maximum Operating Humidity
    • ±93 Percentage
  • Light Bulb Type
    • LED
  • Addressing Style
    • ANN-Bus Unique
  • Number of Zones
    • 10 Zones
  • Light Bulb Type : LED
  • Addressing Style : ANN-Bus Unique
  • Number of Zones : 10 Zones
  • Alarm Current : 68 milliampere|28 milliampere
  • Minimum Operating Humidity : ±2 Percentage
  • Maximum Wiring Distance : 6000 foot
  • Maximum Operating Humidity : ±93 Percentage
Sort
Document Title
File Size
Date Added
Asset Language
Content Type
Image
SKU
Description
alt
N-ANN-LED-W
N-ANN-LED Annunciator Module: 24V DC: Alarm: 68 mA: Stand by current : 28 mA: White Enclosure
alt
N-ANN-LED-R
N-ANN-LED Annunciator Module: 24V DC: Alarm: 68 mA: Stand by current : 28 mA: Red Enclosure
alt
N-ANN-LED
N-ANN-LED Annunciator Module: 24V DC: Alarm: 68 mA: Stand by current : 28 mA: red/trouble yellow/supervisory yellow