/content/hbtbt/dk/en/search-results.html

Relay Modules

Apollo Output Unit

Eltek Apollo output units communicate on fire loop to ANX95 and Delta DA apollo. The device is an output/relay output device that is supported by FireWin Explorer.

Overview
Apollo Output Unit communicates on fire loop to ANX95 and Delta DA apollo. The device is an output/relay device that is supported by FireWin Explorer, is polarity dependent and is connected to the fire loop on terminals L+ and L-. The address is programmed via the DIP switch on the device itself. Monitoring resistor 6K2 is connected directly to terminals IP+ and IP- for unit monitoring. For functions other than output/relay output, use the Apollo Switch monitor or Zone monitor.
Product Number
Image
SKU
Description
alt
251401.1
Apollo Output Unit: 1A Relay Output: 17-35V DC: 60(W)x90(H)x150mm(D): 244g
Image
SKU
Description
alt
251401.1
Apollo Output Unit: 1A Relay Output: 17-35V DC: 60(W)x90(H)x150mm(D): 244g