    Eltek Apollo output units communicate on fire loop to ANX95 and Delta DA apollo. The device is an output/relay output device that is supported by FireWin Explorer.

    Overview
    Apollo Output Unit communicates on fire loop to ANX95 and Delta DA apollo. The device is an output/relay device that is supported by FireWin Explorer, is polarity dependent and is connected to the fire loop on terminals L+ and L-. The address is programmed via the DIP switch on the device itself. Monitoring resistor 6K2 is connected directly to terminals IP+ and IP- for unit monitoring. For functions other than output/relay output, use the Apollo Switch monitor or Zone monitor.
    Specifications

    Others

    • Brand
      • Eltek

    Others

    • Brand
      • Eltek
    • Brand : Eltek
    Product Number
    Part Number
    Description
    Add to list
    251401.1
    Apollo Output Unit: 1A Relay Output: 17-35V DC: 60(W)x90(H)x150mm(D): 244g