Centrales de detección de incendio
FRM-1 Intelli Addressable Relay Module
The FRM-1(A) Addressable Relay Module provides the system with a dry-contact output for activating a variety of auxiliary devices, such as fans, dampers, control equipment, etc.
Please sign in to access more documents
Once signed in, you may be able to access additional documents for your account.
Este producto ha sido descatalogado.
The FRM-1(A) Addressable Relay Module provides the system with a dry-contact output for activating a variety of auxiliary devices, such as fans, dampers, control equipment, etc. Addressability allows the dry contact to be activated, either manually or through panel programming, on a select basis.
Features & Benefits:- Built-in type identification automatically identifies these devices to the control panel
- Internal circuitry and relay powered directly by two-wire SLC loop
- LED blink may be deselected globally (affects all devices)
- High noise immunity (EMF/RFI)
- The FCM-1(A) may be used to switch 24-volt NAC power, audio (up to 70.7 Vrms)
- Wide viewing angle of LED
- EMS screws with clamping plates for wiring ease
- Direct-dial entry of address 01– 159 for Flash Scan loops, 01 – 99 for CLIP mode loops
- Speaker, and audible/visual applications may be wired for Class B or A (Style Y or Z)
- UL: S635
- ULC: S3705 (A version only)
- FM Approved
- CSFM: 7300-0028:0219
- MEA: 14-00-E
- FDNY: COA #6067, #6065
Otros
- Brand
- NOTIFIER
- Product Type
- Relay Module
Otros
- Brand
- NOTIFIER
- Product Type
- Relay Module
- Brand : NOTIFIER