/content/hbtbt/gb/en/search-results.html

Pressure Switches & Sensors

Ex-DDCM Differential Pressure Switches

Ex-DDCM differential pressure monitors are suitable for monitoring and controlling differential pressures, flow monitoring and automatic control of filter systems.All differential pressure monitors can also be used in the vacuum range.

Overview

Ex-DDCM Differential Pressure Switches are suitable for monitoring and controlling differential pressures, flow monitoring and automatic control of filter systems. A double chamber system with stainless steel bellows or Perbunan diaphragm detects the difference between the two applied pressures. The desired switching pressure is continuously adjustable within the ranges listed. All differential pressure monitors can also be used in the vacuum range. The switching differential is not adjustable.It comes with a robust housing made of seawater resistant die cast aluminium GD Al Si 12.Mounting is directly on the pressure line or on a flat surface with two 4 mm Ø screws.Note the connection of pressurized lines:P (+) = high pressureS (–) = low pressure

Features & Benefits:
  • The Ex-DDCM series is calibrated for falling pressure. This means that the adjustable switching pressure on the scale corresponds to the switching point at falling pressure.
  • The reset point is higher by the amount of the switching differential.
Certifications:
  • SIL2 according IEC 61508-2
  • IBExU12ATEX1040 according to ATEX 2014/34/EU
  • IECEx IBE 14.0077
Specifications

Others

  • Maximum Operating Ambient Temperature
    • 60
  • Minimum Operating Ambient Temperature
    • -20
  • Scale Calibration
    • falling pressure
  • Brand
    • FEMA
    • Honeywell
  • Pressure Type
    • Differential Pressure, Relative
    • Differential Pressure, Relative
    • Differenzdruck relativ
    • verschildruk relatief
  • Connection Type
    • Internal Thread G1/4 in
  • Switch Configuration
    • 3 A bei 250 , 2 A bei 250 induktiv, 3 A bei 24 V DC, 0,03 A bei 250 V DC
    • 3 A bei 250 , 2 A bei 250 induktiv, 3 A bei 24 V DC, 0,03 A bei 250 V DC
    • SPDT Microswitch; Capacity 2 A Inductive, 3 A Resistive
    • SPDT Microswitch; Capacity 2 A Inductive, 3 A Resistive

Others

  • Maximum Operating Ambient Temperature
    • 60
  • Minimum Operating Ambient Temperature
    • -20
  • Scale Calibration
    • falling pressure
  • Brand
    • FEMA
    • Honeywell
  • Pressure Type
    • Differential Pressure, Relative
    • Differential Pressure, Relative
    • Differenzdruck relativ
    • verschildruk relatief
  • Connection Type
    • Internal Thread G1/4 in
  • Switch Configuration
    • 3 A bei 250 , 2 A bei 250 induktiv, 3 A bei 24 V DC, 0,03 A bei 250 V DC
    • 3 A bei 250 , 2 A bei 250 induktiv, 3 A bei 24 V DC, 0,03 A bei 250 V DC
    • SPDT Microswitch; Capacity 2 A Inductive, 3 A Resistive
    • SPDT Microswitch; Capacity 2 A Inductive, 3 A Resistive
  • Maximum Operating Ambient Temperature : 60
  • Minimum Operating Ambient Temperature : -20
  • Scale Calibration : falling pressure
  • Brand : FEMA|Honeywell
  • Pressure Type : Differential Pressure, Relative|Differential Pressure, Relative|Differenzdruck relativ|verschildruk relatief
  • Connection Type : Internal Thread G1/4 in
  • Switch Configuration : 3 A bei 250 , 2 A bei 250 induktiv, 3 A bei 24 V DC, 0,03 A bei 250 V DC|3 A bei 250 , 2 A bei 250 induktiv, 3 A bei 24 V DC, 0,03 A bei 250 V DC|SPDT Microswitch; Capacity 2 A Inductive, 3 A Resistive|SPDT Microswitch; Capacity 2 A Inductive, 3 A Resistive
Sort
Document Title
Document Type
File Size
Product Number
Image
SKU
Description
alt
EX-DDCM1602
Differential Pressure Switch to ATEX 201434EU, SPCO, SPCO; differential not adjustable; setting range: 20…160 mbar; switching differential: 0,5 ... 15 mbar; max pressure: 3 bar
alt
EX-DDCM252
Differential Pressure Switch to ATEX 201434EU, SPCO, SPCO; differential not adjustable; setting range: 4…25 mbar; switching differential: 0,7 ... 6,5 mbar; max pressure: 0,5 bar
alt
EX-DDCM4
Differential Pressure Switch to ATEX 201434EU, SPCO, SPCO; differential not adjustable; setting range: 1…4 bar; switching differential: 50 ... 300 mbar; max pressure: 25 bar
Image
SKU
Description
alt
EX-DDCM1602
Differential Pressure Switch to ATEX 201434EU, SPCO, SPCO; differential not adjustable; setting range: 20…160 mbar; switching differential: 0,5 ... 15 mbar; max pressure: 3 bar
alt
EX-DDCM252
Differential Pressure Switch to ATEX 201434EU, SPCO, SPCO; differential not adjustable; setting range: 4…25 mbar; switching differential: 0,7 ... 6,5 mbar; max pressure: 0,5 bar
alt
EX-DDCM4