/content/hbtbt/gb/en/search-results.html

Linear Valves

VGF Flanged Globe Valves

VGF flanged globe valves are used for 2-position or modulating control of steam, hot water, or chilled water in closed loop HVAC systems.

Overview

VGF flanged globe valves are used for 2-position or modulating control of steam, hot water, or chilled water in closed loop HVAC systems. They can be operated by a large variety of electric and pneumatic actuators. Three-way valves are available in mixing or diverting flow patterns.

Features & Benefits:
  • ANSI Class 125 and Class 250 flanged cast iron bodies
  • Face-to-face flange dimensions per ANSI/ISA S75.03 standard
  • Sizes from 2-1/2 to 6 inches (DN65 to DN150)
  • Metal-to-metal seating for long life span
  • Differential pressure of 175 psi, ANSI Class IV leakage on pressure balanced models
  • Steam inlet pressure up to 100 psig (689 kPa)
  • Self-adjusting packing
  • Equal percentage and linear flow characteristics to ensure precise control in a variety of applications