/content/hbtbt/gb/en/search-results.html
    false
    false
    false

    Enclosure Mounts & Hardware

    Fire Protection Housing

    Fire Protection Housing

    Overview

    The duration of the functional integrity of the electrical wiring systems for safety-related systems is at least 30 minutes for:

    - Fire alarm systems including the associated transmission paths.

    - Systems for alerting and issuing instructions to visitors and employees, provided that these systems must be effective in the event of a fire.

    Fire alarm systems required by building law that are provided with esserbus®-PLus alarm devices can be installed in this fire protection housing in accordance with DIN 4102-2 with approval according to DIBt. The housing is a component the VdS device approval and, as a approved distributor, guarantees the alarm systems are supplied for more than 30 minutes.

    Features & Benefits:
    • Fire resistance F30, certified in accordance with DIN 4102-2
    • Functional integrity of over 30 minutes, in accordance with DIN 4102-12
    • Fire load insulation of over 30 minutes in accordance with DIN 4102-11
    • Flexible mounting-rail system for IQ8Control, Compact and FlexES Control FACP
    • Silent ventilation system
    • Push rod fastener with 2-point interlock
    • Cable chute for bundle inlet on the top and under the bottom
    Part Number
    Description
    Leaf Category
    Thumbnail
    Add to list