Monitors
300 Series Monitor Module
Monitor Modules are intended for use in intelligent, two-wire systems where the individual address of each module is selected using the built-in rotary switches. They offer either two-wire or four-wire fault-tolerant Initiating Device Circuit (IDC).
Please sign in to access more documents
Once signed in, you may be able to access additional documents for your account.
Monitor Modules use to monitor a zone of four-wire smoke detectors, manual fire alarm pull stations, water flow devices, or other normally open dry-contact alarm activation devices. They are used to monitor normally-open supervisory devices with special supervisory indication at the control panel. Monitored circuit may be wired as an NFPA Style B (Class B) or Style D (Class A) Initiating Device Circuit. A 47K ohm End-of-Line Resistor (provided) terminates the Style B circuit.
Features & Benefits:- Built-in type identification automatically identifies this device as a monitor module to the control panel
- Powered directly by two-wire SLC loop. No additional power required
- High noise (EMF/RFI) immunity
- SEMS screws with clamping plates for ease of wiring
- LED flashes green during normal operation and latches on steady red to indicate alarm
- UL: S1570
- ULC: S1570
- FM Approved
- CSFM: 7300-0554:131
- MEA: 130-00-E
- FDNY: COA