/content/hbtbt/au/en/search-results.html

    Fire Suppression Devices

    Cable Kit

    Inert Suppression System

    Overview

    The manoswitch (combined pressure gauge and pressure switch) used by Fire Eater features a single pole change over switch making it possible to monitor for normal and low pressure as well as short circuitry and open circuit. Older manoswitches (no CE mark) only features a switch which is closed when pressure is normal. The manoswitches are designed to be connected in a daisy chain, where low pressure on one manoswitch will indicate low pressure on the monitoring panel. The dual-resistor terminator (part of this kit) has to be placed on the last manoswitch in the daisy chain. In the normal position (pressure above the set point) the resistance of the circuitry is high (200Ω/3K3Ω/5K6Ω/10KΩ), when pressure falls below the set point the resistance of the circuitry falls to low (100Ω/680Ω/470Ω/470Ω). Note: Ω = ohm.

    Features & Benefits:
    • Cable kit: Manosw 470R-5K6 2m,
    Certifications:
    • UL & FM
    Name
    Date
    Size
    No Resources documents tagged to this product
    An error occurred . Please try after sometime

    _blank

    Brand@brand

    Filters

    Part Number
    Description
    Leaf Category
    Thumbnail
    Add to list