Fire-Lite - ECC-50/100 Main Console Trouble

Problem:

Why do I get a Main Console Trouble?
How do I clear a main console trouble?
What does it mean when Main Console Trouble LED is lit up?
 

Environment:

  • ECC-50/100
  • Main Console
  • System Trouble
  • Default ECC

Solution:

1.- Confirm customer has resistors in place:

Terminal Blocks with 1 resistor

  • TB4 > 4,7K Ohms (On the in terminals if not being used, on the out terminals if being used)
  • TB5 > 4,7K Ohms (On the in terminals if not being used, on the out terminals if being used)
  • TB19 > 4,7K Ohms (On B+- Terminals if not being used, at EOL if being used)
  • TB20 > 15K Ohms (On the out Terminals if not being used, at EOL if being used)
  • TB21 > 15K Ohms (On the out Terminals if not being used, at EOL if being used)
  • TB22 > 15K Ohms (On the out terminals if not being used, at EOL if being used)
  • TB23 > 4,7K Ohms (On B+- Terminals if not being used, at EOL if being used)

Terminal Blocks with 2 resistors 

  • TB6 > 4.7K (One on terminals 1 and 2, another one on terminals 3 and 4)
  • TB7 > 4.7K (One on terminals 1 and 2, another one on terminals 3 and 4)
  • TB8 > 4.7K (One on terminals 1 and 2, another one on terminals 3 and 4)

image.png
2.- If the trouble hasn't cleared after checking resistors > Load Defaults > Send to Panel on the ECC on the following categories:

  • General/NAC Options
  • Address Assignment
  • Message Buttons


image.png

image.png

3.- Re-Program the ECC-50/100 after loading defaults on the following categories:

  • General/NAC Options
  • Address Assignment
  • Message Buttons

Send to Panel each configuration and log off twice when finished.

image.png
4.- If loading defaults doesn't clear the trouble:

  • Turn SW3 to the down position
  • Wait 30 seconds
  • Turn SW3 back up
  • Power the ECC-50/100 down for a minute
  • Power unit back up


image.png