/content/hbtbt/us/en/search-results.html

    Air Quality Sensors

    Searchpoint Optima Plus Point Infrared Gas Detector

    Discontinued

    An advanced, Point-Infrared, flammable Hydrocarbon gas detector certified for use in potentially explosive atmospheres

    Overview
    This product has been discontinued.
    Honeywell will provide product support until
    Due to unprecedented demand and production capacity constraints, we are currently experiencing longer lead times on our range of Searchpoint Optima Plus point infrared gas detectors. Currently, the extended lead time for Searchpoint Optima Plus instruments is 12 weeks from date of order. Honeywell estimates that this extended lead time will continue until early Q1 2026.

    Product Overview:
    Infrared point hydrocarbon gas detector certified for use in potentially explosive atmospheres.
    With over 40 years experience in the design, manufacture, installation and maintenance of point infrared gas detection, Honeywell Analytics currently has a worldwide installed base of over 100,000 infrared point hydrocarbon gas detectors in a wide spectrum of applications from light industrial to the most demanding of offshore environments.
    Searchpoint Optima Plus is an infrared point Hydrocarbon gas detector certified for use in potentially explosive atmospheres. The unit’s infrared detection principle offers the fastest speed of response and fail-to-safe operation, ensuring that your plant is compliant, your personnel are protected and your production process can deliver maximum uptime. Reduced routine maintenance, when compared with conventional electro-catalytic based gas detectors, provides low ongoing cost of ownership. The development of advanced internal fault diagnostics and false alarm rejection algorithms ensures that the Searchpoint Optima Plus delivers the highest level of operational integrity.
    Typical Applications:
    Offshore oil and gas platforms, floating production storage and offloading (FPSO) vessels, tankers, onshore oil and gas terminals, refineries, LNG/LPG bottling plants, gas compressor/metering stations, gas turbine power plants, solvent printing and coating plants.
    Over 100 gas and vapor calibrations available. For a list of gases and vapors that Searchpoint Optima Plus can detect, contact your local distributor.
    Additional Features and Benefits:
    Why Searchpoint Optima Plus is the right choice...
    • Experience gained from over 100,000 units installed worldwide
    • Improved reliability
    • Optional HART® over 4-20mA output
    • Can detect a wide range of hydrocarbon gases including solvents
    • Increased reliability with no moving parts
    • Increased stability from self compensating optics
    • Immune to long term component drift
    • Remote functional gas test facility
    • Certified for North American and European Hazardous areas
    • Increased false alarm rejection
    • Increased uptime with contaminated optics warning
    • Dynamic Heating Control ensures condensation free optics
    • No undetected failures
    • Improved diagnostics
    • Integral event logging
    • Reduced power consumption
    • Certified to many hazardous area classification schemes including: UL, CSA, ATEX, IECEx and more
    Why Infrared?
    • Failsafe operation
    • Fast speed of response
    • Reduced routine maintenance
    • Immune to catalytic poisons
    • Long operating life
    • Works in inert atmospheres
    Features & Benefits:
    • Over 100,000 units installed worldwide
    • Improved reliability
    • Fast speed of response
    Quick Specs:
    • Material: 316 stainless steel
    • Response time: T50 < 3 seconds, T90 < 4 seconds (methane)
    • Operational and certified: -40° to + 65°C temperature range
    Fire and Gas Consultancy Services
    Even the best products deserve expert maintenance!
    Elevate your gas detectors’ potential with Honeywell's expert maintenance services! Maximize uptime, eliminate costs, and ensure on-time, on-budget project completion.
    Explore our fixed, portable, and high-tech support services now!
    Specifications

    Overview

    • Brand
      • Honeywell
      • Honeywell

    Features

    • Sub-Category
      • Infrared Gas Detectors & Transmitters
      • Infrared Gas Detectors & Transmitters
    • Alarm Settings
      • Fault: 0 mA (Hart® Units Adjustable to 1 mA)
      • Inhibit: 1-3mA (Default 2 mA)
      • Over Range: 20-21.5 mA (Default 21 mA)
      • Warning: 0 to 6 mA (Default 3 mA)
    • Features & Benefits
      • Can Detect a Wide Range of Hydrocarbon Gases Including Solvents
      • Certified for North American and European Hazardous areas
      • Dynamic Heating Control Ensures Condensation Free Optics
      • Failsafe Operation
      • Fast Speed of Response Provides Earliest Warning
      • Immune to Catalytic Poisons
      • Immune to Long Term Component Drift
      • Improved Diagnostics
      • Improved Reliability
      • Increased False Alarm Rejection
      • Increased Reliability with No Moving Parts
      • Increased Stability from Self Compensating Optics
      • Increased Uptime with Contaminated Optics Warning
      • Integral Event Logging
      • Long Operating Life
      • No Undetected Failures
      • Optional HART® Over 4 to 20 mA Output
      • Reduced Power Consumption
      • Reduced Routine Maintenance
      • Remote Functional Gas Test Facility
      • Works In Inert Atmospheres
    • Repeatability
      • < ±2% fsd @50% fsd

    Dimensions & Weight

    • Weight range
      • 1.6 kg

    Technical Specifications

    • Output Signal Range
      • 4 to 20 mA Autosensing Sink or Source
    • Digital Communication Ports
      • UV/IR
    • Accuracy
      • Optima Plus (Ethylene): Baseline < ±2% fsd, 50% fsd <±3% fsd
      • Optima Plus (Hydrocarbon): Baseline < ±1% fsd, 50% fsd <±2% fsd
    • Measuring Range
      • 0-100% LEL
    • Digital Output
      • Modbus RS485 (via XNX, Optional HART® over 4 to 20 mA output (HART® Version 7)

    Operating Characteristics

    • Minimum Temperature
      • -40˚C

    Material Specifications

    • Material
      • 316 Stainless Steel
    • Enclosure Material
      • Plastic

    Standards & Certifications

    • Ingress Protection
      • IP66/67

    Electrical Specifications

    • Power Requirement
      • 18 to 32 VDC

    Others

    • Industry
      • Energy
      • Healthcare
      • Manufacturing

    Overview

    • Brand
      • Honeywell
      • Honeywell

    Features

    • Sub-Category
      • Infrared Gas Detectors & Transmitters
      • Infrared Gas Detectors & Transmitters
    • Alarm Settings
      • Fault: 0 mA (Hart® Units Adjustable to 1 mA)
      • Inhibit: 1-3mA (Default 2 mA)
      • Over Range: 20-21.5 mA (Default 21 mA)
      • Warning: 0 to 6 mA (Default 3 mA)
    • Features & Benefits
      • Can Detect a Wide Range of Hydrocarbon Gases Including Solvents
      • Certified for North American and European Hazardous areas
      • Dynamic Heating Control Ensures Condensation Free Optics
      • Failsafe Operation
      • Fast Speed of Response Provides Earliest Warning
      • Immune to Catalytic Poisons
      • Immune to Long Term Component Drift
      • Improved Diagnostics
      • Improved Reliability
      • Increased False Alarm Rejection
      • Increased Reliability with No Moving Parts
      • Increased Stability from Self Compensating Optics
      • Increased Uptime with Contaminated Optics Warning
      • Integral Event Logging
      • Long Operating Life
      • No Undetected Failures
      • Optional HART® Over 4 to 20 mA Output
      • Reduced Power Consumption
      • Reduced Routine Maintenance
      • Remote Functional Gas Test Facility
      • Works In Inert Atmospheres
    • Repeatability
      • < ±2% fsd @50% fsd

    Dimensions & Weight

    • Weight range
      • 1.6 kg

    Technical Specifications

    • Output Signal Range
      • 4 to 20 mA Autosensing Sink or Source
    • Digital Communication Ports
      • UV/IR
    • Accuracy
      • Optima Plus (Ethylene): Baseline < ±2% fsd, 50% fsd <±3% fsd
      • Optima Plus (Hydrocarbon): Baseline < ±1% fsd, 50% fsd <±2% fsd
    • Measuring Range
      • 0-100% LEL
    • Digital Output
      • Modbus RS485 (via XNX, Optional HART® over 4 to 20 mA output (HART® Version 7)

    Operating Characteristics

    • Minimum Temperature
      • -40˚C

    Material Specifications

    • Material
      • 316 Stainless Steel
    • Enclosure Material
      • Plastic

    Standards & Certifications

    • Ingress Protection
      • IP66/67

    Electrical Specifications

    • Power Requirement
      • 18 to 32 VDC

    Others

    • Industry
      • Energy
      • Healthcare
      • Manufacturing
    • Brand : Honeywell|Honeywell
    • Sub-Category : Infrared Gas Detectors & Transmitters|Infrared Gas Detectors & Transmitters
    • Weight range : 1.6 kg
    • Output Signal Range : 4 to 20 mA Autosensing Sink or Source
    • Minimum Temperature : -40˚C
    • Alarm Settings : Fault: 0 mA (Hart® Units Adjustable to 1 mA)|Inhibit: 1-3mA (Default 2 mA)|Over Range: 20-21.5 mA (Default 21 mA)|Warning: 0 to 6 mA (Default 3 mA)
    • Features & Benefits : Can Detect a Wide Range of Hydrocarbon Gases Including Solvents|Certified for North American and European Hazardous areas|Dynamic Heating Control Ensures Condensation Free Optics|Failsafe Operation|Fast Speed of Response Provides Earliest Warning|Immune to Catalytic Poisons|Immune to Long Term Component Drift|Improved Diagnostics|Improved Reliability|Increased False Alarm Rejection|Increased Reliability with No Moving Parts|Increased Stability from Self Compensating Optics|Increased Uptime with Contaminated Optics Warning|Integral Event Logging|Long Operating Life|No Undetected Failures|Optional HART® Over 4 to 20 mA Output|Reduced Power Consumption|Reduced Routine Maintenance|Remote Functional Gas Test Facility|Works In Inert Atmospheres
    • Material : 316 Stainless Steel
    • Digital Communication Ports : UV/IR
    • Accuracy : Optima Plus (Ethylene): Baseline < ±2% fsd, 50% fsd <±3% fsd|Optima Plus (Hydrocarbon): Baseline < ±1% fsd, 50% fsd <±2% fsd
    • Ingress Protection : IP66/67
    • Repeatability : < ±2% fsd @50% fsd
    • Power Requirement : 18 to 32 VDC
    • Measuring Range : 0-100% LEL
    • Industry : Energy|Healthcare|Manufacturing
    • Enclosure Material : Plastic
    • Digital Output : Modbus RS485 (via XNX, Optional HART® over 4 to 20 mA output (HART® Version 7)
    Name
    Date
    Size
    No Resources documents tagged to this product
    An error occurred . Please try after sometime

    _blank

    Filters

    Product Number
    Part Number
    Compare
    Description
    Leaf Category
    Thumbnail
    Add to list
    002-2101-000
    COVER PGM UNIT HEAD SOFT
    002-2101-000
    COVER PGM UNIT HEAD SOFT
    008-2126-010
    RING,ADHESIVE TAPE,4R LEL SENSOR, 10PK
    008-2126-010
    RING,ADHESIVE TAPE,4R LEL SENSOR, 10PK
    008-3015-010
    PROBE,SAMPLE PROBE WITHOUT TUBING
    008-3015-010
    PROBE,SAMPLE PROBE WITHOUT TUBING
    008-3058-000
    KIT,ADH TAPE RING + FILTER,4R LEL SENSOR
    008-3058-000
    KIT,ADH TAPE RING + FILTER,4R LEL SENSOR
    04200-A-0145
    ANALOG OUTPUT MODULE SINK 5704, OPTIMA
    04200-A-0145
    ANALOG OUTPUT MODULE SINK 5704, OPTIMA
    04200-A-0146
    ANALOG OUTPUT MODULE SOURCE 5704, OPTIMA
    04200-A-0146
    ANALOG OUTPUT MODULE SOURCE 5704, OPTIMA
    04200-A-1015
    OPTIMA (ATEX) DUCT MOUNT KIT NO JB
    04200-A-1015
    OPTIMA (ATEX) DUCT MOUNT KIT NO JB
    04200-A-1040
    OPTIMA ADAPTER PLATE
    04200-A-1040
    OPTIMA ADAPTER PLATE
    04200-N-0008
    OPTIMA UL SS STANDARD BAFFLE
    04200-N-0008
    OPTIMA UL SS STANDARD BAFFLE
    04230-A-1001
    HAND HELD INTERROGATOR ATEX
    04230-A-1001
    HAND HELD INTERROGATOR ATEX