Current Sensors
Vertical Sash Sensor OEM
Vertical sash sensor used on vertical frame of the fumehood for OEM partner.
Please sign in to access more documents
Once signed in, you may be able to access additional documents for your account.
Phoenix Controls Sash Sensors detect a fume hood’s sash position. Sensors can be configured to operate with the sash configurations found on most VAV fume hoods. The sash sensors are used together with a Phoenix Controls fume hood monitor and airflow control valve to maintain a constant average face velocity at the sash opening
A precision potentiometer coupled with a stainless steel, nylon-jacketed cable that attaches to the vertically rising fume hood sash or counterweight cable. As the sash moves, the reel/potentiometer rotates and changes resistance. A variable sash position voltage is received by the fume hood monitor. Multiple sashes are located side-by-side and can be of unequal width
Features & Benefits:- Direct reel sash sensing technology
- Stainless steel, nylon-jacketed cable coupled to a ten-turn precision potentiometer.Available in two types:
- Standard throw: maximum retraction of 41 in (1041 mm).
- Long throw: maximum retraction of 100 in (2540 mm).
- 0-10,000 ohm output proportionate to sash position
- Two to eight 10K ohm reels are provided with a DH/V for multiple side-by-side configurations.
- Tested for 475,000 life cycles
- 22 AWG two-wire, PVC-jacketed signal cable factory wired (12 ft., 3.6 meters)
- Surface or bracket mount (bracket not included) on top of hood
- Dimensions:
- Standard throw: 2.10" H x 2.50" L x 2.00" W (52 x 64 x 51 mm)
- Long throw:4.75" H x 4.70" L x 3.10" W (121 x 119 x 79 mm)
- 0-50 °C (32-122 °F) ambient
- Color: Light gray